DC CHARACTERISTICS
NOMINAL Float Voltage
Recharge Time
By pass ( optional ) |
72V/120V 120 v /192
8 hrs. for 100 % recover
Manual |
192/240V/360V
8 hrs. for 100 % recover
Manual |
360 V
8 hrs. for 100 %recover
Manual |
Output
O/P Voltage / regulation
Full Load Current
Nominal Frequency
Power Factor
Over Load
Static Voltage Regulation
Wave Form
Total Harmonic distortion
Inverter Efficiency
Crest Factor
Change
Battery
Inverter
Indicators
Metering
Display ( optional) |
230V +-1%
Rated At 0.8 PF
50 HZ +/-0.5Hz
0.8p.F
125 % for 10 minutes & 150 % for 1 minute
+/-6% for 50 % step load change
+/-1% for Nominal for all variations of Line load
Sine wave
For linear loads < 2.5 %. For non linear loads < 5 %
85 % to 93 % on full load depending on capacity
1:4
Input Circuit, Breaker Charger, Over voltage, charger over current limit.
Phase sequence (3 Phase).
Battery low cut off / current limit, HRC fuse in battery path, Battery Over charge trip.
Output over voltage / over load trip. Current limit , S.C.Protection
Mains ON , Battery Low , Inverter ON, Fault/ Trip
Output Voltmeter, Output AMMETER ( Optional)
LCD display |
Input
Voltage Range
Power Factor
Frequency |
230 V +/-20 In single phase
At 0.8 TYPICAL
50 Hz +/-3 Hz |
415V, +/-25 % -30 % in three phase
At 0.8 TYPICAL
50 Hz +/-3 Hz |